A dead outlet and a $20 multimeter

A dead outlet, a first multimeter, and a lesson in what a voltage tester can and can't tell you.

The situation

An outlet that had worked fine was suddenly dead. I had never used a multimeter, and a cheap non-contact voltage tester told me the slot was “live”, which only made things more confusing.

Why the tester misled me

A non-contact detector senses the field around the hot conductor and says nothing about the neutral. An outlet can have hot present and still be dead, because the return path is broken. That is the classic signature of an open neutral, or of an outlet downstream of something that has cut power.

The order that worked

  1. Learn what normal looks like first. Before probing the dead outlet, I measured one I knew worked. Seeing about 120 V there meant I knew the meter, the probes and my technique were right.
  2. Check upstream GFCIs. A tripped GFCI in the garage, bathroom or kitchen can kill outlets in other rooms without tripping a breaker. Press Reset on every one, even ones that look fine.
  3. Flip every wall switch in the room. Switch-controlled outlets are common, and the switch may be one you never use.
  4. Measure the slots:
MeasurementReadingMeaning
Hot to neutralabout 120 VOutlet is fine; the problem is the device
Hot to groundabout 120 V, but hot to neutral near 0 VOpen neutral: broken return upstream
Both near 0 VnoneOpen hot, or an upstream GFCI or connection
Hot to neutral reads 120 V but drops under loadsagsLoose or corroded connection

The answer

It was a wall switch. The outlet was switch-controlled, and the switch was off. With the switch on, the outlet read 121 V. No tools were needed to fix it, only to prove it.

What I took from it

Stop and call an electrician for any burnt smell, melted plastic or scorch marks, or an open neutral you can't find in the box. A floating neutral can carry dangerous voltage even when everything looks dead. I'm not an electrician, and this is what worked for one outlet, not advice for your wiring.